SALIENT FEATURES OF SUARHLIAP WSS
(Solar Pumping Scheme)
- Administrative Approval and Expenditure Sanction : No.B.17021/4/2018-PHE Dt.19th Oct. 2018 under NEDP
- Total Estimated and Approved Amount : Rs 130.00 lakhs
- Design Population : 1124 souls
- Design Discharge : 0.0675 mld
- Date of Starting : Feb. 2019
- Date of Completion : Dec. 2020
Major Physical works:
- Intake - 1no
- Gravity Main of 65mm dia GI Pipe
- Treatment Plant (Horizontal Roughing Filter)
- Clear Water Sumps - 1nos(1no of 50,000 lit cap)
- Rising (Pumping) Main of 65mm dia GI Pipes
- 1nos of Reservoirs (1lac lit cap)
- Distribution System/Feeding Main, Public Points of 11nos.
- Approach Road of 0.50 Kms
- Solar Power Plant – 1no
Details of Solar power Plant & Machineries:
- 45nos of PV Modules : Pmpp - 325W, Voc – 46.2V, Isc – 9.13A, Vmpp – 37.8V, Impp – 8.6A, FF – 77.07%, Eff – 16.75%, Dimension – (1956x992x36)mm, Model – ELDORA VSP.72.325.03.04, Company - VIKRAMSOLAR
- 2nos of Electric Motors : (380-415)V, (30.2-30.5)A, (2860-2900)rpm, (0.89-0.81)pf, 15KW, Model: AC-S6-15, LORENTZ, Germany
- 2nos of Pumps: Discharge - 12 m3/hr (Max), Head – (200-280)m, LORENTZ, Germany
TRIAL RUN :
Dt.16th Dec. 2020 (fri) hian Er. Lalzawmliana, Sr. Executive Engineer, Mamit WATSAN Division, PHED leh P & V Eastern Engineer, Bawngkawn, Aizawl te chuan Suarhliap WSS (SOLAR PUMPING) chu hlawhtling takin an enchhin ta, Chipui Lui atangin Suarhliap khawchung MAIN RESERVOIR ah a Pump chhuak a, nitin TUI litre 50,000 atanga 1,20,000 Pump theih beisei a ni. Nizung chakna (Solar) hmanga tui hi Pump tur a nih avangin, khaw that leh that lovah tui Pump chhuah zat hi a danglam thei a ni.